Sign In | Join Free | My xxjcy.com |
|
Categories | Active Power Filter |
---|---|
Brand Name: | CONSNANT |
Model Number: | 50A - 300A |
Certification: | ISO CE |
Place of Origin: | Shenzhen China |
MOQ: | 10 |
Price: | Negotiable |
Payment Terms: | L/C, T/T, Western Union |
Supply Ability: | 500 pieces per month |
Delivery Time: | 20-30 days against thr order quantity |
Packaging Details: | export standard carton box |
Nominal volt.: | 380×(1±15%)V |
Wires: | Three or Four |
Active power loss: | <5% |
Communication: | RS485 PC interface, remote control function |
Display: | LCD monitoring panel; parameters setting online; touchable button operation; multi-parameter display |
Reactive power compensating: | Determined by priority |
Mult - protection Intelligent Active Power Filter Auto. / Manual Working Mode
Snapshots:
AC Input:
Rated voltage: 380×(1±15%)V
Rated Frequency: 50×(1±1%)Hz
Rated topology: Three-phase three-wire
Function Features:
Why Choose Us?
We have experienced team for more ten years and high-tech equipment.
Our products is with ICE, ISO and Chinese TLC
We can make product according to your requirements, such as your size, color, design, and your logo.
Technical Details:
Output current capacity(A) | 45 | 75 | 100 | 150 | 200 | |
AC Input | Rated voltage | 380×(1±15%)V | ||||
Rated Frequency | 50×(1±1%)Hz | |||||
Rated topology | Three-phase three-wire | |||||
Technical | orders of harmonic compensating | Within 5~13: selectable Or within 5~25: all compensation | ||||
Compensating rate (THDILoad-THDIS)/ THDILoad | ≥85% | |||||
Reactive power compensating | Determined by priority | |||||
Full response time | ≤20ms | |||||
Overload Protection | Automatically limited to the rated output current | |||||
Active power loss | <5%Rated capacity | |||||
Noise | <65dB | |||||
Environment & | Operating temperature | -10OC~+45OC | ||||
Storing Temperature | -20OC~+65OC | |||||
Relative humidity | <90%(25OC) | |||||
Working Mode | Automatically or manually | |||||
Communication Interface | RS485 PC interface, remote control function | |||||
Operation Display | LCD monitoring panel; parameters setting online; touchable button operation; multi-parameter display | |||||
Display Accuracy | ±2%FS | |||||
Expansion Ability | Directly connect in parallel with the same model machine | |||||
Protection | Grid over-voltage, Grid under-voltage, Grids missing phase, Grid wrong phase, the Machine over current and overheating | |||||
Protection level | IP20 | |||||
dimension mm(W×H×D) | 600×1200×400 | 600×2200×600 | 800×2200×600 | |||
Non-standard sizes can be customized | ||||||
Weight(kg) | 150 | 200 | 400 |
![]() |