CPT-III Current Transformer and Voltage Potential Transformer Testing Equipment

Categories Transformer Testing Equipment
Brand Name: Delta
Model Number: CPT-III
Certification: ISO9001
Place of Origin: China
MOQ: 1 set Relay Tester
Price: USD1.0
Payment Terms: T/T, Western Union
Supply Ability: 1000 sets per month
Delivery Time: 10-20 days
Packaging Details: CPT-III Current Transformer Testing packed in veneer case
Item Name: CPT-III Current Transformer and Voltage Potential Transformer Testing Equipment
Functions: Test parameters of various kinds of transformer
Description: Power Current Transformer Testing Equipment
Knee Point Voltage: 40kV
Max. Test Voltage: 180V
Size: 485mm×356mm×183mm
Weight: <15kg
Power supply: AC220V ± 10%, 50Hz/60Hz
Warranty: One year
Service: OEM service is available
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

CPT-III Current Transformer and Voltage Potential Transformer Testing Equipment

CPT-III Current Transformer and Voltage Potential Transformer Testing Equipment

Introduction:

CPT-III Current Transformer and Voltage Potential Transformer Testing Equipment is used to measure all kinds of current transformer and voltage transformer.

CPT-III Current Transformer and Voltage Potential Transformer Testing Equipment can calculate the ratio errors and phase angle errors of current transformer and voltage transformer at rated burden and working burden in one test.

CPT-III Current Transformer and Voltage Potential Transformer Testing Equipmentcan automatically evaluate the test results according to the selected standard to determine whether the transformer is qualified.

Application:

Tests for current transformer:

  1. Excitation curve and parameters test
  2. Turns ratio test
  3. Ratio and phase error test
  4. Polarity mark check
  5. Winding resistance measurement
  6. Secondary loop burden measurement
  7. Error line curve test for protection CT
  8. Transient CT parameters test
  9. CT nameplate guess
  10. Saturation hysteresis loop curve measurement

Tests for voltage transformer:

  1. Turns ratio test
  2. Ratio error and phase angle error test
  3. Polarity test
  4. Secondary burden test
  5. Winding resistance test

Applications for CTPT analyzer:

  • CT nameplate check
  • CT parameters check in work burden
  • CT transient parameters analysis
  • CT ratio and phase error calibration
  • PT routine test


Parameters:

1Test standardsIEC60044-1, IEC60044-6, GB1208, GB16847, C57.13
2Power supplyAC220V±10%,50Hz/60Hz±10%
3Power output0.1~180V (AC)
4Current output0.001~5A(RMS)
5Power output300VA
6Max. knee voltage measurement45kv
7Current measurement range0~10A (automatically change range in 0.1/0.4/2/10A)
8Current measurement error<±0.1%+0.01%FS
9Voltage measurement range0~200 V (automatically change range in 1V/10V/70V/200V)
10Voltage measurement error< ±0.1%+0.01%FS
11Turns ratio measurement range

1~35000;

1~2000 error<0.05%;

2000~5000 error>0.1%;

5000~35000 error<0.2%

12Phase measurementerror:±2min,resolution:0.01min
13Coil resistance measurement

Range: 0~8kΩ(automatically change range in 2ohm /20ohm /80ohm/800ohm/8kohm)

Error< 0.2%RDG+0.02%FS

Maximum resolution: 0.1mΩ

14Temperature measurement-50~100 Celsius degree, error<3 Celsius degree
15CT Secondary burden

Range 0-160ohm (automatically change range in 2ohm/ 20ohm/80ohm/160ohm)

Error <0.2%RDG+0.02%FS

Maximum resolution 0.001ohm

16PT Secondary burden

Range 0-80kohm (automatically change range in 800ohm / 8kohm /80kohm)

Error <0.2%RDG+0.02%FS

Maximum resolution: 0.1ohm

17PT ratio measurement

Range: 1~35000,

1~5000 error<0.2%

5000~35000 error<0.5%

18Saved data groups>1000groups
19Work conditionTemperature:-10℃-50℃, moist:≤90%
20Size485mm×356mm×183mm
21Weight<15Kg

CPT-III Current Transformer and Voltage Potential Transformer Testing Equipment Real Picture:



Quality CPT-III Current Transformer and Voltage Potential Transformer Testing Equipment for sale
Send your message to this supplier
 
*From:
*To: Delta Technology (Chongqing) Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0